Evaluation of the Grounding System for the RRI Palembang Transmitter Tower Based on Resistance Measurements and Safety Standards

  • Tondi Hatorangan Siregar Universitas Palembang
  • Dian Eka Putra Universitas Palembang
  • Daeny Septy Yansuri Universitas Palembang
  • Raden Ahmad Yani Universitas Palembang
Keywords: Grounding resistance, transmission tower, RRI Palembang, soil resistivity, PUIL 2020, lightning protection

Abstract

The grounding system on radio transmission towers plays a crucial role in protecting equipment from lightning strikes and ensuring personnel safety. This study evaluates the grounding resistance of the existing RRI Palembang transmission tower, estimates soil resistivity, compares it with the PUIL 2020 and IEEE standards, and proposes optimization measures where necessary. Resistance measurements were taken using the Fall of Potential method with a Kyoritsu 4105A Earth Tester at three different times (noon, afternoon, and night) under clear weather conditions. Soil resistivity was estimated from the resistance data and the existing electrode configuration. The results showed average resistance values of 0.080 Ω (daytime), 0.390 Ω (afternoon), and 0.793 Ω (nighttime). All of these values are below the maximum limits set by PUIL 2020 (5 Ω for general installations, 1 Ω for lightning protection) and IEEE Std 142-2007 (1 Ω). Estimated soil resistivity values of 0.84–8.30 Ωm indicate highly conductive soil. The Ground Potential Rise (GPR) voltage during a 30 kA lightning strike reached a maximum of 23.8 kV, which is still within safe limits. With a safety factor of 1.26 relative to lightning protection standards, the existing grounding system is deemed excellent and does not require significant optimization. This study demonstrates that the soil conditions around the tower are highly favorable for the grounding system.

Keywords: Grounding resistance, transmission tower, RRI Palembang, soil resistivity, PUIL 2020, lightning protection

References

R. A. Yani, D. E. Putra, R. M. E. Suherman, and J. Ardian, “Penggunaan Arrester Sebagai Pengaman Gardu Distribusi 20 KV Pada Trasformator 160 KVA di Penyulang Akasia,” AMPERE, vol. 9, no. 2, pp. 141–149, 2024, doi: http://doi.org/10.31851/ampere.

D. E. Putra, R. A. Yani, M. S. Siahan, C. Rizal, and N. Nofiansah, “The Decreasing Ground Potential Rise by Lessening Soil Resistance in Arrester Grounding System,” IJEEIT Int. J. Electr. Eng. Inf. Technol., vol. 6, no. 2, pp. 44–50, 2023, doi: 10.29138/ijeeit.v6i2.2180.

R. Saragih, Yusniati, R. Nasution, and Armansyah, “Study of Lightning Protection Equipment Lightning Arresters in 20 KV Distribution Networks,” J. Electr. Technol., vol. 5, no. 1, pp. 32–36, 2020.

I. A. Satya Wicaksana, I. Arta Wijaya, and I. Janardana, “Analisis Sistem Pembumian Tower Saluran Transmisi Dari Gardu Induk Kapal – Gardu Induk Gianyar,” J. SPEKTRUM, vol. 8, no. 4, p. 57, 2022, doi: 10.24843/spektrum.2021.v08.i04.p7.

IEEE-SA Standards Board, “IEEE Std 142TM-2007: Recommended Practice for Grounding of Industrial and Commercial Power Systems.,” ANSI Stand, vol. 2007, 2007, [Online]. Available: https://ieeexplore.ieee.org/document/4396963

BSN, “Persyaratan Umum Instalasi Listrik 2020 (PUIL 2020),” DirJen Ketenagalistrikan, vol. 2020, no. PUIL, pp. 1–850, 2020.

D. E. Putra, Y. Randika, I. Randika, and H. Inamullah, “Enhancing grounding system efficiency through biopore technique in seasonal soil conditions,” Int. J. Adv. Technol. Eng. Explor., vol. 11, no. 113, 2024, doi: http://dx.doi.org/10.19101/IJATEE.2023.10102391.

G. U. Hardi, T. Taufiq, Raihan Putri, and F. A. Nasution, “Pengaruh Tahanan Jenis Tanah Terhadap Sistem Pentanahan Menggunakan Elektroda Batang Dilokasi Gedung Teknik Elektro Unimal,” INSOLOGI J. Sains dan Teknol., vol. 2, no. 2, pp. 314–326, 2023, doi: 10.55123/insologi.v2i2.1818.

IEEE Std 81, IEEE Std. 81- Guide for Measuring Earth Resistivity , Ground Impedance , and Earth Surface Potentials of a Grounding System IEEE Power and Energy Society, vol. 2012, no. December. 2012.

Junaidi, D. E. Putra, and C. Rizal, “Tinjauan Perbandingan Resistansi Pentanahan antara Perencanaan dan Hasil Uji Komisioning Di Gardu Distribusi 20 kV,” J. Ampere, vol. 9, no. 1, pp. 18–24, 2024, doi: http://doi.org/10.31851/ampere.