PENERAPAN IEEE 519-2014 TERHADAP IDENTIFIKASI DISTORSI HARMONISA PADA TRANSFORMATOR 3 FASA
Abstract
Transformator merupakan peralatan yang paling merasakan adanya harmonik, karena letaknya yang lebih dekat terhadap beban. Pada transformator, harmonik arus (THD% I) akan menyebabkan peningkatan rugi-rugi tembaga (Cu), sedangkan harmonik tegangan (THD% V) menyebabkan peningkatan rugi-rugi arus Eddy (Eddy Current) sehingga terjadi kerugian daya dan peningkatan temperatur. Pada penelitian ini dilakukan untuk mengetahui gangguan harmonik pada transformator 3 phasa dari pemakaian beban non linier dengan cara mengidentifikasi tingkat dominan harmonik, THD % arus maupun tegangan, peningkatan temperatur dan estimasi kerugian daya yang dimonitoring secara real-time menggunakan software IoT Blink. Hasil pengujian menunjukkan bahwa harmonisa arus pada transformator 3 phasa menimbulkan rugi – rugi tembaga (Cu) sebesar 0,0424 pu (setara 57,98 W) dan rugi arus eddy sebesar 0,0370 p.u (setara 50,60W).
An author who publishes in the Jurnal Teknik Elektro (JTE) agrees to the following terms:
Author retains the copyright and grants the journal the right of first publication of the work simultaneously licensed under the Creative Commons Attribution-ShareAlike 4.0 License that allows others to share the work with an acknowledgement of the work's authorship and initial publication in this journal.
Submission of a manuscript implies that the submitted work has not been published before (except as part of a thesis, report, or abstract); that it is not under consideration for publication elsewhere; that its publication has been approved by all co-authors. If and when the manuscript is accepted for publication, the author(s) still hold the copyright and retain publishing rights without restrictions. For the new invention, authors are suggested to manage its patent before publication. The license type is CC-BY-SA 4.0.
Jurnal Teknik Elektro (JTE)is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.